Wattcor W211 / W212

More Information

"zero crossing" switching

The Wattcor W211 / 212 line offers highly reliable solid state power control with “zero crossing” switching up to 600A / 660Vac for resistive loads. The units are ideally suited for repetitive, wear and tear free switching of heater banks. The most outstanding features of these switches are low heat dissipation and compact, space saving construction.

The W211 is triggered by a logic signal (5-30 VDC or Vac). Three phase loads can be controlled by two or three W211 units.

The W212 is controlled by an analogue signal (0-5V, 0-10V, 0 / 4-20mA) or potentiometer. The output switches in bursts (“zero crossing” switching) and the duty cycle is proportional to the input signal. The cycle time of the output can be adjusted by a trimmer incorporated in the unit. Three phase loads can be controlled by using one W212 as master and one or more W211 as slaves. The master unit synchronizes the slave units.

Common Features:

  • Compact construction, space saving
  • Low power dissipation (1.2W / A)
  • Zero crossing switching
  • Logic "Power disabled" input
  • "RPC" (optional) partial load failure detection
  • "DTC" (optional) short circuit or current failure detection
  • "DE" (optional) electronic overload protection up to 13x nominal current
  • Alarm relay output for fault conditions
  • Internal fuse with fuse failure output (on 250A and 600A units)
  • DIN rail mounting (25A to 150A units)
  • Panel mounting (250A to 600A units)

General Features:

Nominal working voltage: 660Vac (max. range 20...725Vac)

Nominal frequency: 50/60Hz 

Current Ratings (50°C)
Model Repetitive
overcurrent
(t= 1s)
Non- repetitive
overcurrent
(t= 20ms)
I't for fusing
(t=1-10s)
Critical dv/dt
with output
de- activated
24 Arms

≤ 74A

≤ 600A

1800A2s

1000V/µs

40Arms

≤ 100A

≤1500A

11200A2s 1000V/µs
75Arms

≤ 180A

≤ 1700A

14450A2s1000V/µs
100Arms

≤ 300A

≤ 4800A

86200A2s1000V/µs
150Arms

≤ 300A

≤ 4800A

86200A2s1000V/µs
250Arms

≤ 450A

≤ 7800A

200000A2s1000V/µs
400Arms

≤2000A

≤ 15000A

1125000A2s500V/µs
600Arms

≤ 2000A

≤ 15000A

1125000A2s

500V/µs

Temperature derating curves