Two different parallel watt density cables may be spliced together. Being parallel, the power out put in the two spliced sections will be different as rated. Care must be taken to not exceed the maximum circuit length and circuit breaker rating. The simple solution in this case is to use the maximum circuit length of the higher wattage cable.